BEV
bus
CHP
CIP
CNG
NOX
ORC
RES
    Print  

MARUŠA, R., VORŠIČ, J., PIHLER, J., KOBAL, I., MARUŠA, L.
SELECTION OF A SUITABLE CONDUCTOR FOR GROUNDING THE CABLE SHIELD TO THE TRANSMISSION LINE TOWER
KOMUNALNA ENERGETIKA / POWER ENGINERING, 16
This paper describes which factors to consider when faced with choosing conductor for grounding of surge arresters and high-voltage cables on powerline construction, where transition between powerline construction and powerline cable takes place. For proper grounding of surge arrester and shielded cable, the grounding cables have to be designed to ensure efficient high frequency current flow to the ground that can reach up to 10 kA. During our research and measurements we have chosen such a conductor that at the same time ensures recommended parameters and is not of any particular value to vandalism.

MARUŠA, R., BEZJAK, S., BOBIČ, T., MARUŠA, L., BUČAR, A., BELAK, L.
PRACTICAL PREPARATION OF ELECTRICAL INSTALLATION REMOTELY CONTROLLED CONSUMPTION OF ENERGY
KOMUNALNA ENERGETIKA / POWER ENGINERING, 22
Smart Grid and. smart grids are theoretically in full swing, but the practical electrical installations in the users do not adequately adapted to the technology of remote control. In this paper we moved directions and applications designed to be remotely controlled certain electricity consumers even at installations in the domestic take-up of electricity.

MARUŠA, R., VORŠIČ, J., PIHLER, J., FERLIČ, R., BELAK, L., RIBIČ, J., MARUŠA, L.
TESTING SLIDING GROUNDING CLAMP FOR EARTHING CONDUCTORS TO DOUBLE-CIRCUIT 110 KV TRANSMISSION LINE
KOMUNALNA ENERGETIKA / POWER ENGINERING, 20
This paper presents the testing Sliding clamps for grounding conductor transmission line. For the purpose of an effective transmission line grounding in working with vicinity of high voltage a special form of sliding clamps for grounding has been designed. Grounding device is intended for grounding transmission line conductors, which are dragged along conductor installation on a double-circuit transmission line, the second system operates normally which represents a significant risk for single-phase ground fault . The device must provide such a connection during the sliding along the guide, so that it prevents the arc and effectively discharges ground current into the ground. Prior to regular usage, it was necessary for grounding the device to perform a series of tests, which are described in this article. A test with the realization of single-phase ground fault was also carried out on the transmission network of 110 kV ELES. All tests have been successful and positive.

  HOME MEETING SCHEDULE CONTENT PRESENTATION ARCHIVE E-REGISTRATION